Bỏ qua tới nội dung

Giải pháp điện lực với vi ba và IP6704A

Nghiên cứu tình huống của Loop Telecom – nội dung giữ nguyên bản tiếng Anh. Cần tư vấn bằng tiếng Việt, vui lòng liên hệ kỹ sư NQC.

Solution for Power Utilities With Microwave Radio and IP6704A Equipment

Situation:

A customer needed to implement a new communication system to transport teleprotection signals, integrating a new substation SITE C 110KV to its Carrier Wave link from SITE A 110KV to SITE B 110KV.

Solution:

The solution was a Microwave communication system in free band between SITE A 110KV and SITE C 110 KV, with a distance of 4 km, and the current Carrier Wave communication system will be relocated between SITE C 110KV and SITE B 110KV, with a distance of 132 km.

Overview

The system consists of two free band radio links with 1+1 protection that will communicate between the substations SITE A 110 KV and SITE C 110KV.

The main and backup radio links will be selected by the IP6704A equipment; this device will be in charge of monitoring the status of the main channel in such a way that when a failure occurs, it will automatically switch to the backup link, generating an alarm that will inform the control center of the situation.

The C37.94 interfaces available in the IP6704A equipment at each of the sites will be used to send Teleprotection signals.

Components of the system:

← Điện lực

Trao đổi với kỹ sư NQC

Cần tư vấn cấu hình thiết bị truyền dẫn?

Kỹ sư NQC hỗ trợ bằng tiếng Việt: chọn model, card cắm thêm, báo giá.
Yêu cầu báo giá