Situation:
A customer needed to implement a new communication system to transport teleprotection signals, integrating a new substation SITE C 110KV to its Carrier Wave link from SITE A 110KV to SITE B 110KV. 
Solution:
The solution was a Microwave communication system in free band between SITE A 110KV and SITE C 110 KV, with a distance of 4 km, and the current Carrier Wave communication system will be relocated between SITE C 110KV and SITE B 110KV, with a distance of 132 km.
Overview
The system consists of two free band radio links with 1+1 protection that will communicate between the substations SITE A 110 KV and SITE C 110KV.
The main and backup radio links will be selected by the IP6704A equipment; this device will be in charge of monitoring the status of the main channel in such a way that when a failure occurs, it will automatically switch to the backup link, generating an alarm that will inform the control center of the situation.
The C37.94 interfaces available in the IP6704A equipment at each of the sites will be used to send Teleprotection signals.
Components of the system: